News Information

Example of lightning current in TT system

2022-12-29

Common mode SPD between phase and PE or phase and PEN is installed whatever type of system earthing arrangement (see Fig. 1).

 

The neutral earthing resistor R1 used for the pylons has a lower resistance than the earthing resistor R2 used for the installation.

 

The lightning current will flow through circuit ABCD to earth via the easiest path. It will pass through varistors V1 and V2 in series, causing a differential voltage equal to twice the Up voltage of the SPD (Up1 + Up2) to appear at the terminals of A and C at the entrance to the installation in extreme cases.

 


Fig. 1 – Common protection only


To protect the loads between Ph and N effectively, the differential mode voltage (between A and C) must be reduced.

 

Another SPD architecture is therefore used (see Fig.2)

 

The lightning current flows through circuit ABH which has a lower impedance than circuit ABCD, as the impedance of the component used between B and H is null (gas filled spark gap). In this case, the differential voltage is equal to the residual voltage of the SPD (Up2).

 


Fig.2 – Common and differential protection



We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies. Privacy Policy
Reject Accept